1.1 This fire-test-response test method measures the performance of a unique fire resistive joint system called a continuity head-of-wall joint system, which is designed to be used between a rated wall assembly and a nonrated horizontal assembly during a fire resistance test.

1.2 This fire-test-response standard does not measure the performance of the following:

1.2.1 The rated wall assembly, which is already established by other test methods, such as Test Method E119, or

1.2.2 The nonrated horizontal assembly, which would be established by other test methods such as Test Method E119.

Note 1: Typically, rated wall assemblies obtain a fire resistance rating after being tested to Test Method E119, NFPA 251, UL 263, CAN/ULC-S101, or other similar fire resistive test methods.

1.3 This fire-test-response standard is not intended to evaluate the connections between rated wall assemblies and nonrated horizontal assemblies unless part of the continuity head-of-wall joint system.

1.4 The fire resistive test end point is the period of time elapsing before the first performance criteria is reached when the continuity head-of-wall joint system is subjected to one of two time-temperature fire exposures.

1.5 The fire exposure conditions used are either those specified by Test Method E119 for testing assemblies to standard time-temperature exposures or Test Method E1529 for testing assemblies to rapid-temperature rise fires.

1.6 This test method specifies the heating conditions, methods of test, and criteria to establish a fire resistance rating only for a continuity head-of-wall joint system.

1.7 Test results establish the performance of continuity head-of-wall joint systems to maintain continuity of fire resistance of the rated wall assembly where the continuity head-of-wall joint system interfaces with a nonrated horizontal assembly during the fire-exposure period.

1.8 Test results shall not be construed as having determined the continuity head-of-wall joint system, nonrated horizontal assembly and the rated wall assembly's suitability for use after that fire exposure.

1.9 This test method does not provide quantitative information about the continuity head-of-wall joint system relative to the rate of leakage of smoke or gases or both. However, it requires that such phenomena be documented

Product Details

Published:
04/01/2017
Number of Pages:
16
File Size:
1 file , 490 KB
Note:
This product is unavailable in Russia, Ukraine, Belarus

Document History

ASTM E2837-13(2017)

ASTM E2837-11

ASTM D2290-04

ASTM D2290-04

Standard Test Method for Apparent Hoop Tensile Strength of Plastic or Reinforced Plastic Pipe by Spl..

$30.00 $60.00

ASTM A543/A543M-93(2004)e1

ASTM A543/A543M-93(2004)e1

Standard Specification for Pressure Vessel Plates, Alloy Steel, Quenched and Tempered Nickel-Chromiu..

$26.00 $52.00

ASTM C201-93(2004)

ASTM C201-93(2004)

Standard Test Method for Thermal Conductivity of Refractories..

$30.00 $60.00

ASTM D2346-00(2004)

ASTM D2346-00(2004)

Standard Test Method for Apparent Density of Leather..

$26.00 $52.00